Using Voltara Intelligence · Reference

Numbers card

The headline figures and the checks behind them. From Lesson 8; checked in the app on 2026-10-18.

What each tile is

TileBuilt fromWatch for
Generation MTD / YTDSum of daily rowsLabel runs to today even when data stops earlier
PREach day's stored PR, weighted by irradiance × capacity; days with POA under 0.5 or over 10 kWh/m², or PR over 110%, left outTyped PR is never recalculated
AvailabilityCapacity weighted, valid days onlyOver 100% of target is possible (target 99%)
CUFEnergy ÷ (capacity × 24 h × calendar days so far)Missing days count as zero
MTD vs budgetEnergy ÷ prorated budgetPlants without a budget still add energy on top
PM complianceTasks done ÷ tasks dueCounts tasks, not started or safe rounds

The PR check

PR = energy (MWh) ÷ (capacity (MWp) × irradiance (kWh/m²))

Example: 578.5 ÷ (120.4 × 5.91) = 81.3%. If the stored PR differs by more than a point or two, one of the three figures is wrong.

Five checks before you quote a figure

  1. Banner: which plants are stale or missing?
  2. Coverage: how many days are really measured?
  3. Source: feed or typed? (Logbook: notes and status)
  4. Arithmetic: recalculate PR for any odd day.
  5. Comparison: which plants and days are in the denominator?

Daily figures (Logbook)